Telbit Smart-Bulk
meter wiring guide.

Find the correct colour-coded wiring, pulse factor and totalizer setup for a supported water meter or sensor.

Reviewed 29 September 2026 by the Smart-View Technology technical team.

One clear field workflow
  1. 01Choose the meter
  2. 02Match the wires
  3. 03Configure the device

Find your meter or sensor

Select the exact model before wiring.

Before you connect

Isolate power where required, confirm the exact meter model and pulse factor, and follow all site safety procedures. Use suitable gel-filled connectors for the wire joints.

01 / 09

Cyble Sensor V2

Itron Cyble Sensor V2 fitted to TD8 and Flostar M meters.

01

Wire the meter to Smart-Bulk

Match pulse to pulse and ground to ground on the appropriate channel.

Cyble Sensor V2meter side
WHITEPulse
BROWNGround
Smart-BulkPrimary input
YELLOWPulse
BLUEGround

Selected variant: 1 L/pulse.

02

Configure the Smart-Bulk

Use the keypad commands in this order.

26# · 1#Set the pulse factorEnter 26#, then 1# to set 1 L/pulse.
3# or 4#Set the totalizerUse 3# to sync readings below 9 999.999 m³ in litres. For higher bulk-meter readings, use 4# to sync in cubic metres.
14#Set the number of m³ countersChoose the counter count that matches the mechanical totalizer and required resolution.
03

Confirm the counter resolution

The number of mechanical counters determines range and device resolution.

CountersMechanical totalizerDevice resolutionDevice totalizer
49 999.999 m³1 L or 0.001 m³9 999.999 m³
599 999.99x m³1 L or 0.001 m³99 999.999 m³
6999 999.9xx m³10 L or 0.01 m³999 999.99 m³
79 999 999.xxx m³100 L or 0.1 m³9 999 999.9 m³

Still unsure about compatibility?

Send our team the meter model, size, K-factor and clear photos of the meter face and output wires.

Contact Smart-View